Brand | Wone Store |
Model NO. | DC Molded Case Circuit Breaker |
Rated frequency | 50/60Hz |
Series | DCM |
Description
DC molded case circuit breakers are suitable for circuits with a rated operating voltage up to DC1500V, a rated insulation voltage of 1500V, a rated impulse withstand voltage of 12kV, and a rated current ranging from 10A to 630A. They can be installed either vertically or horizontally and are resistant to environments containing humid air, salt spray, oil mist, mold, and the like.
Technical Parameter
Rated Operating Voltage Ue(V,AC) |
DC250V | DC1000V | DC1500V | DC1500V | DC1500V | ||
Rated insulation voltage Ui (V): |
1000V | 1500V | 1600V | 1600V | 1600V | ||
Rated Shock Withstand Voltage Uimp (kV): |
0.8kV | 0.8kV | 1.2kV | 1.2ky | 1.2ky | ||
Rated Operating Short Circuit Segmentation Capability LCS (%LCU) |
DC110V | 35kA | |||||
DC250V | 25kA | ||||||
DC500V | 35kA | ||||||
DC750V | 25kA | 85kA | 85kA | 85kA | |||
DC1000V | 15kA | 50kA | 50kA | 50kA | |||
DC1200V | 35kA | 35kA | 35kA | ||||
DC1500V | 20kA | 20kA | 20kA | ||||
Rated Limit Short-Circuit Segmentation Capability lcu (kA): |
DC110V | 35kA | |||||
DC250V | 25kA | ||||||
DC500V | 35kA | ||||||
DC750V | 25kA | 85kA | 85kA | 85kA | |||
DC1000V | 15kA | 50kA | 50kA | 50kA | |||
DC1200V | 35kA | 35kA | 35kA | ||||
DC1500V | 20kA | 20kA | 20kA | ||||
Operational performance (times) |
Electrical examination | 5000 times | 2000 times | DC1000V2000 times DC1500V1000 times |
DC1000V2000 times DC1500V1000 times |
DC1000V2000 times DC1500V1000 times |
|
Mechanical examination | Exemption from maintenance and examination | 10,000 times | 10,000 times | 10,000 times | 10,000 times | 10,000 times | |
It can maintain the life of the exam | 20,000 times | 20,000 times | 20,000 times | 15,000 times | 15,000 times |
Normal working conditions
For altitudes of 2000m and below, the capacity reduction coefficient at high altitude is shown in the volume reduction coefficient table;
Model | Shell Grade Current Rating (A) | 50℃ | 55℃ | 60℃ | 65℃ | 70℃ |
GYM7DC-125/2300 | 250 | 1 | 0.95 | 0.93 | 0.91 | 0.88 |
GYM7DC-250/2300 | 250 | 1 | 0.95 | 0.93 | 0.91 | 0.88 |
GYM7DC-320/2300 | 250 | 1 | 0.95 | 0.93 | 0.91 | 0.88 |
GYM7DC-400/2300 | 400 | 1 | 0.93 | 0.91 | 0.89 | 0.85 |
GYM7DC-630/2300 | 630 | 1 | 0.92 | 0.90 | 0.89 | 0.83 |
Storage temperature -40°C ~+75°C;
The relative humidity of the air at the installation site should not exceed 50% at the temperature of +40°C, and it can be at lower temperaturesHigher relative humidity, e.g. 90% at 20°C. Measures should be taken against occasional condensation due to temperature changes;
TH (three-proof type) meets the requirements of GB/T2423.4 and GB/T2423.18 standards, and can withstand humid air, salt spray,the influence of oil mist and mold;
The inclination is ±22.5°;
In a medium without explosion hazard, and the medium is not enough to corrode the metal and destroy the insulation of gas and conductive dust Place;
In a place where there is no rain and snow.
Product Dimensions