• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How to Solve Single-Phase Grounding Fault Judgment for 3-Phase 4PT in Ungrounded Systems?

Felix Spark
Field: Failure and maintenance
China

In 10 kV and 35 kV ungrounded systems, single - phase grounding faults cause minimal current, so protection rarely trips. Per regulations, operation is limited to 2 hours; prolonged undetected faults may worsen, even damaging switches. While the State Grid promotes small - current grounding line selection devices in 110 kV and 220 kV substations, their accuracy remains low, requiring monitoring/operation staff to analyze remote measurements. For ungrounded systems with three - phase 4PT voltage transformers, this paper analyzes single - phase grounding to improve remote measurement usability for staff, offering solutions based on field experience.

1 Analysis of Normal Operation and Single - Phase Grounding Faults in Ungrounded Systems
1.1 Voltage Transformer Principle During Normal Operation

For a 10 kV bus three - phase 4PT voltage transformer (wiring: Figure 1), UA, UB, UC(phase - to - ground voltages), UL (zero - sequence voltage); UAa, UBb, UCc (primary winding phase voltages); Ua, Ub, Uc (secondary winding phase voltages), 3U0 (zero - sequence voltage). All PT ratios:(10 kV/√3)/(57.74 V).

During normal operation, the primary three - phase and zero - sequence voltages are analyzed, as shown in Equation (1). From Equation (1), the secondary voltages are obtained as Ua= 57.74 V, Ub = 57.74V, Uc = 57.74V, and 3U0 = 0V, which are consistent with the secondary voltages of the voltage transformer with a three - phase open - delta connection.

1.2 Principle Analysis of PT in Single - Phase Grounding

When a phase - A grounding fault occurs, the primary side of the voltage transformer can be equivalently represented as shown in Figure 2. Among them, the primary windings of the three - phase PT are , the zero - sequence winding impedance is , and UA', UB', UC', UL' are the phase - to - ground voltages of the three phases and the zero - sequence voltage when a phase - A grounding fault occurs, respectively.

According to the superposition theorem, it can be obtained that

According to the characteristics of the three - phase 4PT voltage transformer, the impedance of the zero - sequence winding is much larger than that of the phase winding. Then the above formula can be simplified as shown in Formula (3).

When a phase - A grounding fault occurs, the phase - to - ground voltage of phase A is 0, and the voltages of phases B and C are 10 kV. Combined with Formula (3), the phasor diagram during the single - phase grounding fault can be obtained, as shown in Figure 3.

According to the phasor diagram analysis in Figure 3, Formula (4) can be obtained. Among them, UAa', UBb', and UCc' are the primary winding voltages of the bus after the phase - A grounding fault, respectively.UAa'= UA 10kV√3, UBb'= UB 10kV√3, UCc' =UC 10kV√3, UL'=UA = 10kV √3. Converting to the secondary side after the fault, we can get Ua' = 57.74V, Ub' = 57.74V, Uc' = 57.74V, and 3U0' = 57.74V.

From the above analysis, in an ungrounded system, when a single - phase grounding fault occurs, the voltages of the three phases ABC are all 57.74 V, which is consistent with the normal operation situation. Only the zero - sequence voltage rises to the phase voltage, which brings great confusion to monitoring and operation and maintenance personnel. It is very difficult to judge that it is a single - phase grounding fault. Moreover, because the fault current is too small for the protection to start the protection tripping, it brings hidden dangers to the safe and stable operation of the power grid.

2 Rectification Measures

To solve the problem that, for the voltage transformer with the three - phase 4PT wiring mode, when a single - phase grounding fault occurs, the uploaded three - phase voltage remote measurement is consistent with the normal operation situation, which brings certain confusion to monitoring and operation and maintenance personnel. This paper proposes to keep the wiring mode of the primary side voltage winding of the three - phase 4PT voltage transformer unchanged and change the wiring of the secondary winding, as shown in Figure 4.

Based on the principle analyzed in Section 1.2, we can derive: UA' = UL' + UAa' = 0V, UB' = UL' + UBb' = 10kV, UC' = UL' + UCc' = 10kV. That is, the secondary voltages after the fault are UA' = 0V, UB' = 100 kV, UC' = 100kV, and3U0' = 57.74kV. From the data analyzed above, for the improved three - phase 4PT voltage transformer, during a single - phase grounding fault, the three - phase voltages are consistent with those of a single - phase fault in a three - phase four - wire system, and the zero - sequence voltage also rises to the phase voltage.

Monitoring and operation and maintenance personnel can quickly determine that a single - phase grounding fault has occurred in the 10 kV system. Combined with the small - current grounding line selection device, the relevant fault line can be removed as soon as possible.

3 Conclusion

This paper proposes a secondary winding wiring method for the three - phase 4PT voltage transformer, which can upload three - phase voltage remote measurements with the same characteristics as those of a single - phase grounding fault in an ungrounded system to the monitoring system. Thus, it is more conducive for monitoring and operation and maintenance personnel to make quick judgments, prevent the fault from worsening further, and ensure the safe and stable operation of the power grid.

Give a tip and encourage the author!
Recommended
Ultimate Guide to AC Contactor Abnormal Noise: From Electromagnetic Noise to Mechanical Vibration, Accurate Diagnosis and Handling
In electrical control systems, AC contactors are among the commonly used electrical components, and they are also a common source of various electrical faults. After long-term use—especially in harsh environments with high levels of dust—AC contactors may sometimes emit squeaking or rattling noises after being pulled in and held. The causes of this phenomenon are analyzed as follows.Squeaking Noise After Pull-In and HoldingA fully functional AC contactor makes no noise when energized and pulled
Felix Spark
09/11/2025
Comprehensive Guide to High-Frequency Fault Handling of AC Contactors: 90% of Problems Solved with One Method
1. Fault Phenomena, Cause Analysis and Handling MethodsContactor does not operate or operates abnormally after coil energization Open circuit in coil control circuit; Check if there is wire breakage or loosening at the terminal blocks. If there is a wire breakage, replace the corresponding wire; if there is loosening, fasten the corresponding terminal block. Coil damage; Measure the coil resistance with a multimeter. If the resistance is ∞, replace the coil. Thermal relay not reset after operati
Felix Spark
09/11/2025
Application and Maintenance of AC Contactors | Comprehensive Analysis of Common Fault Handling, Master It in One Article
1 Analysis of Key Components of AC ContactorsAn AC contactor is an automated electromagnetic switch used for long-term, high-frequency switching of AC main circuits and control circuits. It features advantages such as automatic operation, under-voltage and no-voltage protection, high-capacity operation, strong stability, and low maintenance requirements. In the electrical control circuits of machine tools, AC contactors are mainly used to control electric motors and other loads.The key component
Felix Spark
09/11/2025
Dielectric Withstand Capability of AC Vacuum Contactors and Countermeasures
During operation, AC vacuum contactors are often subjected to various overvoltages such as lightning overvoltage and switching overvoltage. Therefore, AC vacuum contactors must have a certain voltage withstand capacity.An AC vacuum contactor is composed of a vacuum interrupter (its structure is shown in Figure 1), a housing, an electromagnetic system, a secondary circuit, and other components. Among these, the vacuum interrupter is the "heart" of the AC vacuum contactor, and its performance dire
Felix Spark
09/09/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.