Design The Foundations of Transmission Towers

Encyclopedia
Field: Encyclopedia
0
China

Foundation Design Definition


The foundation design for transmission towers involves creating stable bases using RCC, designed to withstand various loads and soil conditions.

 


Different Soil Types


Transmission tower foundations must adapt to different soil types like black cotton soil, fissured rock, and sandy soil, each requiring unique construction methods.

 


Dry Fissured Rock


Foundations in dry fissured rock need special considerations like undercuts and anchor bars for stability.

 


Stability Factors


Ensuring stability against sliding, overturning, and buoyancy is crucial, with specific safety factors for normal and short circuit conditions.

 


Protective Measures


Additional protection for foundations is necessary in aggressive soils to prevent damage and ensure longevity.

 


Design of Foundation of Transmission Towers in Different Soils

 


  • All foundation shall be of RCC. The design and construction of RCC structures shall be carried out as per IS:456 and minimum grade of concrete shall be M-20.



  • Limit state method of design shall be adopted.



  • Cold twisted deformed bars as per IS:1786 or TMT bars shall be used as reinforcement.



  • Foundations shall be designed for the critical loading combination of the steel structure and or equipment and/or superstructure.



  • Protection should be provided to foundations when needed, especially for aggressive soils like alkaline soil, black cotton soil, or any soil harmful to concrete foundations.



  • All structures must be checked for stability against sliding and overturning during construction and operation under various load combinations.



  • When checking for overturning, consider the weight of the soil above the footing, but do not include the inverted frustum of the earth on the foundation.



  • Base slab of any underground enclosure shall also be designed for maximum ground water table. Minimum factor of safety of 1.5 against bouncy shall be ensured.


  • Tower and equipment foundations must have a safety factor of 2.2 for normal conditions and 1.65 for short circuit conditions to prevent sliding, overturning, and pullout.

 

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso