• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is a Phase Synchronizing Device?

Encyclopedia
Field: Encyclopedia
0
China


What is a Phase Synchronizing Device?


Phase Synchronizing Device Definition


A Phase Synchronizing Device (PSD) is defined as a device that synchronizes the switching of circuit breaker poles to the zero crossing of the phase voltage or current waveform.


Controlled Switching Device


Also known as a Controlled Switching Device (CSD), it ensures accurate timing during circuit breaker operations.


Voltage and Current Synchronization


The PSD uses voltage and current waveforms to identify zero crossings and synchronize breaker operations accordingly.


When switching off a circuit breaker to cut an inductive load, it’s best to interrupt the current at the zero crossing of the current waveform. However, this is difficult to achieve exactly. In normal circuit breakers, current interruption occurs near, but not exactly at, the zero crossing point. Because the load is inductive, this sudden interruption causes a high rate of current change (di/dt), resulting in high transient voltage in the system.


c9c04418569008f87aa07c25b8fbd190.jpeg


In low or medium voltage power systems, transient voltage during circuit breaker operation may not significantly affect performance. However, in extra and ultra-high voltage systems, it is more impactful. If the circuit breaker contacts are not sufficiently separated at the moment of interruption, re-ionization can occur due to transient overvoltage, leading to re-established arcing.


When we switch on an inductive load like transformer or reactor, and if the circuit breaker closes the circuit near to the voltage zero crossing, there will be high DC component of current. This may saturate the core of transformer or reactor. This leads to a high inrush current in the transformer or reactor.


When connecting a capacitive load, like a capacitor bank, it’s best to switch on the circuit breaker at the zero crossing of the system voltage waveform.

 

c2926e255baf7fcd90674da29785a8fa.jpeg

 

e866b0ce6ab0f753063478d3f7592b4e.jpeg

 

Otherwise due to sudden change in voltage during switching, high inrush current is created in the system. This may be followed by over voltage in the system too.


The inrush current along with over voltage stress mechanically and electrically, the capacitor bank and other equipment in line.


In circuit breaker, all three phases usually open or close almost simultaneously. However, there is a 6.6 ms time gap between the zero crossings of adjacent phases in a three-phase system.


This device takes voltage waveform from potential transformer of bus or load, current waveform from current transformers of the load, auxiliary contact signal and reference contact signal from circuit breaker, closing and opening command from control switch of the circuit breaker installed in control panel.


Voltage and current signal from each phase are required to identify exact instant of zero crossing of the waveform of individual phase. Breaker contact signals are required to calculate the operational delay of the circuit breaker, so that the opening or closing pulse to the breaker can be send accordingly, to match the interruption and zero crossing of either current or voltage wave, as per requirement.


9094d53b3b2a66d5c5cb29fc685f977f.jpeg


This device is dedicated for manual operation of the circuit breaker. During faulty tripping, the trip signal to the circuit breaker is directly sent from the protection relay assembly, bypassing the device. The Phase Synchronizing Device or PSD may also be associated with a bypass switch which can bypass the device from the system if required in any situation.


Inductive Load Management


Switching on inductive loads at the right moment prevents high inrush currents that can damage equipment.


Capacitive Load Switching


Proper timing when switching capacitive loads reduces the risk of high inrush currents and overvoltage.



Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.