• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Method for Automatic Isolation of Customer Equipment Faults by Load Switches in Distribution Networks

Felix Spark
Field: Failure and maintenance
China

1 Overview

Distribution network safety has long been under - addressed, with its automation lagging substation automation . Using 10 kV intervals of existing substations to set line section points meets future grid needs . Configuration of distribution switches, section switches, and protection must match substation outgoing - line protection for reliability. Fault isolation, self - healing, and restoration are key to distribution automation .

Scholars have studied smart distribution network fault - restoration optimization (multi - power, intermittent sources, energy storage) , but not load - switch - based user - equipment fault isolation. Take Figure 1’s line: Section switch S3 serves A, B, C. A’s fault triggers S3 tripping. Transient faults allow successful reclosing; permanent ones cause B/C outages, harming production, cutting supply, and adding troubleshooting (as S3 can’t pinpoint the fault, requiring one - by - one checks).Thus, a load - switch method/device is urgently needed to isolate faults, identify faulty users. Ensure S3 recloses successfully for non - faulty users, regardless of user/fault type (transient/permanent).

2 Method for Effectively Isolating Power User Equipment Faults with Load Switches

A load switch, a switching device between a circuit breaker and an isolating switch, has a simple arc - extinguishing device. It can interrupt rated load current and some overload current but not short - circuit fault current. So, when any user equipment fails, only section switch S3 trips for protection. If a device detects the faulty user and trips its load switch before S3 recloses, the faulty user is isolated, S3 recloses successfully. Sending faulty user info to distribution network operation & maintenance (O&M) personnel via text message lets them handle faults quickly, reducing O&M workload, improving power supply reliability, and ensuring non - faulty users’ power supply.

3 Technical Route for Effectively Isolating Power User Equipment Faults with Load Switches
3.1 Technical Logic Module Process

Take User A’s equipment fault as an example. Install a fault detection device at its load switch (as in Figure 2). Set between the load switch and incoming line, it has a voltage detection module, current detection module, logic judgment & processing module, tripping contact, signaling contact, and wireless signal sending module (logic process in Figure 3). Outputs of voltage and current detection modules connect to the logic module’s input. Its output connects to one end of the tripping contact and signaling contact. The tripping contact’s other end connects to the user’s primary equipment via the load switch’s tripping coil; the signaling contact’s other end connects to the wireless module. This enables effective fault isolation, quick fault handling by maintenance staff, reduced fault - finding workload, and improved work efficiency.

3.2 Physical Wiring Implementation

Taking User A’s equipment fault as an example (see Figure 4), the voltage detection module connects to the bus voltage transformer of the public power distribution room, and the current detection module connects to CT1 (current transformer of User A’s incoming line). User A’s logic judgment module processes the input current and voltage.

When User A has a short - circuit fault, the current through its logic judgment module surges to (and exceeds) the preset fault current, marked as “1”. Then, section switch S3 trips, causing the public distribution room bus to lose voltage. All users’ logic modules detect this voltage loss (marked “1”), but only User A’s module detects both fault current and voltage loss (both “1”). These “1s” form an AND gate, identifying User A as faulty.

User A’s logic module outputs tripping contact TJ1 and signaling contact TJ2. TJ1 closes, connecting to the positive power supply and load - switch tripping coil to trip User A’s load switch. TJ2 closes, sending fault info to distribution network O&M staff via wireless. This ensures the faulty user’s load switch doesn’t interrupt fault current yet isolates the fault. Non - faulty users, despite voltage loss (no fault current detected), don’t trip their load switches (AND gate not activated).

Similarly, the secondary currents of incoming line current transformers CT2 (User B) and CT3 (User C) connect to the detection device. The fault logic follows User A’s principle, isolating faults for B/C to ensure others’ normal power supply.

4 Coordination with Section Switch Protection & Anti - Maloperation Measures

  • For overhead lines: The fault detector coordinates with S3’s reclosing time (typically 1.2s delay post - trip). Within 1.2s, it must trip the faulty user’s load switch (preventing S3 from reclosing on faults). Fault info is texted to O&M staff for quick repairs.

  • For cable lines: Since S3 has no reclosing, the detector trips the faulty load switch and texts fault info. O&M staff then close S3, ensuring non - faulty users’ power and reducing outage time.

  • To avoid mis - tripping non - faulty load switches after S3 recloses: The detector’s logic requires first sensing fault current surge, then voltage loss (forming an AND gate). A delay is added to voltage loss judgment (to prevent mis - trips from inrush current reaching before voltage).

5 Conclusion

Installing fault detectors at users’ incoming line load switches (coordinated with section switch protection) lets load switches auto - isolate faults and alert O&M staff. This boosts public distribution line reliability, cuts troubleshooting workload, and limits outage spread. The device can also be used on main distribution line load switches (coordinated with upper - level section switch protection), isolating post - load - switch faults and ensuring power for users between switches. This shrinks outage ranges and improves distribution line reliability.

Give a tip and encourage the author!
Recommended
Ultimate Guide to AC Contactor Abnormal Noise: From Electromagnetic Noise to Mechanical Vibration, Accurate Diagnosis and Handling
In electrical control systems, AC contactors are among the commonly used electrical components, and they are also a common source of various electrical faults. After long-term use—especially in harsh environments with high levels of dust—AC contactors may sometimes emit squeaking or rattling noises after being pulled in and held. The causes of this phenomenon are analyzed as follows.Squeaking Noise After Pull-In and HoldingA fully functional AC contactor makes no noise when energized and pulled
Felix Spark
09/11/2025
Comprehensive Guide to High-Frequency Fault Handling of AC Contactors: 90% of Problems Solved with One Method
1. Fault Phenomena, Cause Analysis and Handling MethodsContactor does not operate or operates abnormally after coil energization Open circuit in coil control circuit; Check if there is wire breakage or loosening at the terminal blocks. If there is a wire breakage, replace the corresponding wire; if there is loosening, fasten the corresponding terminal block. Coil damage; Measure the coil resistance with a multimeter. If the resistance is ∞, replace the coil. Thermal relay not reset after operati
Felix Spark
09/11/2025
Application and Maintenance of AC Contactors | Comprehensive Analysis of Common Fault Handling, Master It in One Article
1 Analysis of Key Components of AC ContactorsAn AC contactor is an automated electromagnetic switch used for long-term, high-frequency switching of AC main circuits and control circuits. It features advantages such as automatic operation, under-voltage and no-voltage protection, high-capacity operation, strong stability, and low maintenance requirements. In the electrical control circuits of machine tools, AC contactors are mainly used to control electric motors and other loads.The key component
Felix Spark
09/11/2025
Dielectric Withstand Capability of AC Vacuum Contactors and Countermeasures
During operation, AC vacuum contactors are often subjected to various overvoltages such as lightning overvoltage and switching overvoltage. Therefore, AC vacuum contactors must have a certain voltage withstand capacity.An AC vacuum contactor is composed of a vacuum interrupter (its structure is shown in Figure 1), a housing, an electromagnetic system, a secondary circuit, and other components. Among these, the vacuum interrupter is the "heart" of the AC vacuum contactor, and its performance dire
Felix Spark
09/09/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.