How does decreasing the excitation of a synchronous motor affect its current draw?

Encyclopedia
01/11/2025

Effects of Reducing Excitation on Current Consumption in Synchronous Motors

Reducing the excitation of a synchronous motor has significant effects on its current consumption, primarily impacting several key aspects:

1. Changes in Armature Current

The armature current (i.e., stator current) of a synchronous motor consists of two components: active current and reactive current. Together, these determine the total armature current.

  • Active Current: Related to the mechanical power output of the motor, typically determined by the load.

  • Reactive Current: Used to establish the magnetic field, closely related to the excitation current.

When the excitation current is reduced, the strength of the motor's magnetic field weakens, leading to the following changes:

Increase in Reactive Current: To maintain the same power factor, the motor needs to draw more reactive current from the grid to compensate for the weaker magnetic field. This results in an increase in the total armature current.

Current Imbalance: If the excitation is too low, the motor may enter an underexcited state where it not only draws active power but also requires a large amount of reactive power from the grid. This can lead to current imbalance, voltage fluctuations, or instability.

2. Changes in Power Factor

The power factor of a synchronous motor is a crucial indicator of its efficiency. The power factor can be categorized into two states:

Leading Power Factor (Overexcited State): When the excitation current is high, the motor generates excess magnetic flux, causing it to supply reactive power back to the grid, resulting in a leading power factor.

Lagging Power Factor (Underexcited State): When the excitation current is reduced, the motor cannot generate sufficient magnetic flux and must draw reactive power from the grid, resulting in a lagging power factor.

Therefore, reducing the excitation current worsens the motor's power factor (making it more lagging), leading to higher reactive current demand and increased total current consumption.

3. Changes in Electromagnetic Torque

The electromagnetic torque of a synchronous motor is related to both the excitation current and the armature current. Specifically, electromagnetic torque 

T can be expressed as:

d8be36fc6488bab29f30f2a76f401b2f.jpeg

where:

T is the electromagnetic torque,k is a constant,ϕ is the magnetic flux in the air gap (proportional to the excitation current),Ia is the armature current.

When the excitation current is reduced, the air gap magnetic flux ϕ decreases, leading to a reduction in electromagnetic torque. To maintain the same load torque, the motor must increase the armature current to compensate for this loss. Therefore, reducing the excitation current leads to an increase in the armature current, thereby increasing the overall current consumption.

4. Stability Issues

If the excitation current is reduced too much, the motor may enter an underexcited state, potentially leading to a loss of synchronism. In this condition, the motor cannot maintain synchronization with the grid, which can cause severe electrical and mechanical failures. Additionally, the stability and dynamic response of the motor will deteriorate in an underexcited state.

5. Impact on Voltage Regulation

Synchronous motors can regulate grid voltage by adjusting the excitation current. If the excitation current is reduced, the motor's ability to support grid voltage also diminishes, potentially leading to a drop in grid voltage, especially under heavy load conditions.

Summary

Reducing the excitation current of a synchronous motor affects its current consumption in the following primary ways:

  • Increase in Armature Current: Due to the need to draw more reactive current from the grid to compensate for the weakened magnetic field, the total armature current increases.

  • Deterioration in Power Factor: Reducing the excitation current worsens the power factor (making it more lagging), further increasing the demand for reactive current.

  • Reduction in Electromagnetic Torque: To maintain the same load torque, the motor must increase the armature current, leading to increased current consumption.

  • Decrease in Stability and Voltage Regulation Capability: Insufficient excitation can lead to loss of synchronism or voltage instability.

Therefore, in practical applications, it is important to adjust the excitation current appropriately based on load requirements to ensure efficient and stable motor operation. 

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
What are the methods for switching operations of station transformers?
What are the methods for switching operations of station transformers?
Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.The operation method for instantaneous power interruption on the low-voltage side is as follows:Open the 380V power incoming circuit breaker of the corresponding sec
Vziman
07/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!