Starting of an Induction Motor

Edwiin
05/07/2025

Three - Phase Induction Motors: Self - Starting Mechanism and Starting Methods
A three - phase induction motor is inherently self - starting. When the power supply is connected to the stator of a three - phase induction motor, a rotating magnetic field is generated. This rotating magnetic field interacts with the rotor, causing it to start rotating and initiating the operation of the induction motor. At the moment of starting, the motor slip is equal to 1, and the starting current is significantly high.
The role of a starter in a three - phase induction motor extends beyond mere starting. It serves two primary functions:
  1. Current Limitation: It reduces the substantial starting current, which, if left unchecked, could cause damage to the motor windings, overheat electrical components, and create voltage drops in the supply system.
  2. Protection: It provides essential safeguards against overloads, which occur when the motor draws excessive current due to mechanical stress or abnormal operating conditions, and under - voltage situations, where a drop in supply voltage could lead to inefficient motor operation or even stalling.
There are two fundamental approaches to starting a three - phase induction motor. One method involves connecting the motor directly to the full supply voltage. The other approach entails applying a reduced voltage to the motor at startup. It's important to note that the torque produced by an induction motor is proportional to the square of the applied voltage. Consequently, a motor generates significantly more torque when started at full voltage compared to when it is started with reduced voltage.
For cage induction motors, which are widely used in industrial and commercial applications, there are three main starting methods:
Starting Methods for Induction Motors
Direct - on - Line Starter
The direct - on - line (DOL) starter method for induction motors is renowned for its simplicity and cost - effectiveness. With this approach, the motor is directly connected to the full supply voltage. This straightforward method is typically employed for small motors with a rating of up to 5 kW. By using a DOL starter for these smaller motors, potential fluctuations in the supply voltage can be minimized, ensuring stable operation of the electrical system.
Star - Delta Starter
The star - delta starter is one of the most common and widely adopted methods for starting three - phase induction motors. In normal operation, the motor's stator windings are configured in a delta connection. However, during the starting phase, the windings are initially connected in a star configuration. This star connection reduces the voltage applied to each winding, thereby limiting the starting current. Once the motor has gained sufficient speed, the windings are then switched to the delta connection, allowing the motor to operate at its full - rated performance.
Autotransformer Starter
Autotransformers can be used in either star - connected or delta - connected configurations. Their primary function in the context of induction motor starting is to limit the starting current. By adjusting the turns ratio of the autotransformer, the voltage supplied to the motor during startup can be reduced. This controlled reduction in voltage helps to mitigate the high inrush current that occurs when the motor is first energized, protecting both the motor and the electrical supply system.
The direct - on - line, star - delta, and autotransformer starters are specifically designed for cage rotor induction motors, which are prevalent in a wide range of industrial and commercial applications due to their robust construction and reliable operation.
Slip Ring Induction Motor Starter Method
For slip ring induction motors, the starting process involves connecting the full supply voltage across the starter. The unique design of slip ring motors, with their external rotor circuits, allows for additional control during starting. The connection diagram of a slip ring induction motor starter provides a visual representation of how the various components interact to facilitate the starting process, enabling better understanding of its operation and control mechanisms.
When starting a slip ring induction motor, the full starting resistance is initially connected in the rotor circuit. This effectively reduces the supply current drawn by the stator, minimizing the inrush current that could otherwise stress the electrical system and the motor itself. As the electrical supply energizes the motor, the rotor begins to rotate.
As the motor accelerates, the rotor resistances are systematically reduced in stages. This gradual cutting - out of the resistances is carefully coordinated with the increase in the motor's rotational speed. By doing so, the motor can smoothly build up its speed while maintaining optimal torque characteristics.
Once the motor reaches its rated full - load speed, all the starting resistances are completely removed from the circuit. At this point, the slip rings are short - circuited. This short - circuiting allows the motor to operate with maximum efficiency, as it eliminates the additional resistance that was only necessary during the starting phase, enabling the motor to deliver its full - rated performance.
Edwiin

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
What are the methods for switching operations of station transformers?
What are the methods for switching operations of station transformers?
Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.The operation method for instantaneous power interruption on the low-voltage side is as follows:Open the 380V power incoming circuit breaker of the corresponding sec
Vziman
07/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!