In an ungrounded system, what is the return path for the capacitive coupling between the high voltage line and the earth to maintain the flow?

Encyclopedia
Field: Encyclopedia
0
China

In an ungrounded (or isolated grounding) power system, there indeed exists capacitive coupling between high-voltage lines and the earth, forming a capacitive current path. This phenomenon occurs because the electric field between the high-voltage conductors and their surrounding environment, including the ground, causes uneven charge distribution, resulting in what is known as "earth capacitance."

Return Path Through Capacitive Coupling

  1. Earth Capacitance: Each high-voltage line has a certain amount of earth capacitance relative to the ground. These capacitances exist between the conductor and the ground as well as between different conductors. Even without direct electrical connections, capacitive currents arise due to the presence of the electric field.

  2. Capacitive Current Flow: In an ungrounded system, if a single-phase-to-ground fault occurs, the current does not flow directly back to the source through the earth as it would in a grounded system. Instead, it returns to the source via the mutual inductance and capacitance between lines, transformer winding capacitance, and other distributed parameter elements, forming a complete circuit. This process mainly relies on the capacitances between the three-phase conductors and between the conductors and the ground to provide a complete current loop.

  3. System Behavior: In an ungrounded system, when a single-phase-to-ground fault occurs, the fault current is typically very small due to the lack of an effective low-impedance grounding path. The current is primarily a displacement current caused by the aforementioned capacitances. This makes such faults less noticeable initially but could lead to further insulation degradation over time and potentially more severe faults if left unresolved.

  4. Protection Measures: To detect such faults, specialized monitoring equipment, such as ground fault indicators or highly sensitive relay protection devices, are often installed to identify and locate the fault. Additionally, some designs may use a neutral point grounded through an arc suppression coil to limit the fault current during a single-phase-to-ground fault.

In summary, in an ungrounded system, the return path that allows capacitive coupling between high-voltage lines and the earth to maintain current flow is primarily achieved through the capacitances between the conductors and between the conductors and the ground. While this design can reduce certain types of short-circuit currents, it also requires careful monitoring for potential ground faults to ensure timely intervention.

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g
12/15/2025