What is Buchholz Relay in Transformer ?

Encyclopedia
Field: Encyclopedia
0
China

What is Buchholz Relay in Transformer ?

Buchholz relay is a gas relay used in oil-immersed transformers to monitor the gas production inside the transformer, so as to detect possible faults inside the transformer.

How Buchholz relays work

The Buchholz relay works on the basis of the gas produced when the transformer fails internally. When overheating or discharge failure occurs inside the transformer, gas is produced. These gases will rise and pass through the top of the tank into the oil storage tank (oil pillow). In this process, the gas must pass through the Buchholz relay.

Light gas protection: When the gas is slowly produced, the float in the relay will rise as the oil level rises, triggering the light gas protection and usually issuing an alarm signal.

Heavy gas protection: When the gas is produced rapidly, a large amount of gas will speed up the oil flow rate, impact the baffle in the relay, trigger the heavy gas protection, the relay will operate and cut off the power supply of the transformer.

Disposition

Installation Location: The Buchholz relay is installed in the pipe between the transformer tank and the oil storage tank.

Baffle and float: A baffle and float are provided inside the relay to detect gas generation.

Contacts: Contacts inside the relay are used to trigger alarm signals or cut off power.

Exhaust valve: Used to remove gas from inside the relay for maintenance or to remove air after installation.

Maintenance

Periodic check: Check the operating status of Buchholz relays regularly to ensure that they are working properly.

Cleaning: Regularly clean the inside of the relay to remove accumulated gas or dirt.

Exhaust: Periodically open the exhaust valve to discharge the gas inside the relay.

Check: Periodically check the relay to ensure that its operating threshold is correct.

Matters needing attention

Installation position: Ensure that the relay is installed in the proper position to detect gas effectively.

Contact status: Check the status of the contact to ensure that the contact is clean and in good contact.

Cable connection: Make sure the cable connection between the relay and the control system is strong and correct.

Safety operation: When performing maintenance or inspection, follow the safety operation rules to ensure the safety of personnel.

Advantage

Fault detection: Timely detection of faults within the transformer, such as overheating or discharge.

High reliability: Reliable fault detection through simple mechanical structure.

Easy maintenance: Simple structure, easy maintenance and calibration.

Restrict

Misoperation: Misoperation can occur under certain conditions, such as fluctuating oil levels or unstable oil flow.

Sensitivity: May not be sensitive enough for minor faults.

Maintenance and verification

Periodic check: The Buchholz relay is checked regularly to ensure that its performance meets the requirements.

Simulation test: Perform simulated fault test to verify the response ability of the relay.

Maintenance of baffles and floats: Check the status of baffles and floats regularly to ensure that they operate flexibly.

Give a tip and encourage the author!
Recommended
Why Regular Transformer Maintenance Matters: 5 Serious Consequences of Neglecting It
I. Allowable TemperatureWhen a transformer is in operation, its windings and iron core generate copper loss and iron loss. These losses are converted into heat energy, causing the temperature of the transformer's iron core and windings to rise. If the temperature exceeds the allowable value for a long time, the insulation will gradually lose its mechanical elasticity and age.The temperature of each part of the transformer during operation is different: the winding temperature is the highest, fol
Rockwell
09/12/2025
How to Implement Condition-Based Maintenance for Power Transformers? A Complete 4-Step Process Analysis
1. Definition of Condition-Based MaintenanceCondition-based maintenance refers to a maintenance method where decisions on whether and how to perform maintenance are determined based on the real-time operating status and health condition of equipment. It has no fixed maintenance methods or schedules. The prerequisite for condition-based maintenance is the establishment of equipment parameters and the comprehensive analysis of various operational information of the equipment, so as to make reasona
Noah
09/12/2025
Can't choose a dry-type transformer? Get expert advice – free.
Traction Rectifier TransformersRated capacity: 800 to 4400 kVA; Voltage class: 10 kV and 35 kV; Rectifier pulse number: 12-pulse and 24-pulse. Compared with 12-pulse rectifier circuits, 24-pulse rectifier circuits can reduce the harmonic pollution of the power grid by 50%, and no filtering equipment is needed at this location. It is suitable for power supply systems of urban subways and rail transit.Excitation Rectifier TransformersRated capacity: 315 to 3000 × 3 kVA; Voltage class: 10 kV, 13.8
Vziman
09/12/2025
High harmonics? Your transformer may be overheating and aging fast.
This report is based on the analysis of one-day power quality monitoring data of your company's distribution system. The data shows that there is significant three-phase current harmonic distortion in the system (with a high total harmonic distortion of current, THDi). In accordance with international standards (IEC/IEEE), harmonic currents at this level have posed substantial risks to the safe, reliable, and economical operation of the power supply transformer, mainly manifested in additional h
Leon
09/12/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.