What is Commissioning of Power  Transformer ?

Transformer Commissioning Definition

Transformer commissioning is defined as the process of preparing a power transformer for service by conducting various tests and adjusting settings.

340cc900-475e-4749-ba03-730f74821c70.jpg

 Buchholz Relay Test

Buchholz relay operation for alarm and trip should also be checked by injecting air to the test pocket provided in the relay.

Low Oil Level Alarm Test

The low oil level alarm of the magnetic oil gauge should be checked.

Temperature Indicator Test

The contacts of the Oil Temperature Indicator and Winding Temperature Indicator for alarm trip and control should be checked and set at required temperature.

Cooling Gear Test

The IR values and setting for operation of oil pumps and fans motor should be checked.

Alarm trip contact settings of differential pressure gauge, oil and water flow indicators, where provided should be checked.

Marshalling Box

The wiring from various accessories to the Marshalling kiosk should be checked

Protective Relay Test

Trapping of associated circuit breakers is to be provided by actual operation of differential relay, over current relay, earth fault relay and other protective relays as applicable.

Magnetizing Current Test

In the Magnetizing Current Test, measure the magnetizing current by supplying 400 V, three-phase 50 Hz from the HV side while keeping the LV side open-circuited, and then compare the values across different phases.

Additional checks during commissioning of power transformer

  • All oil valves are in correct position closed or opened as required.

  • All air pockets are cleared.

  • Thermometer pockets are filled with oil.

  • Oil is at correct level in the bushing, conservator tank, diverter switch tank etc.

  • Arcing horn of the bushing is set correctly

  • CT polarity is correct when bushing mounted CTs are provided.

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.