What is Transformer Water Content Test?

Encyclopedia
Field: Encyclopedia
0
China

What is Transformer Water Content Test?

Water Content Test Definition

The water content test in insulating oil is defined as a process using Karl Fischer Titration to measure water levels.

17a5077e8ab5adff5c4fbd2e599af959.jpeg

 Karl Fischer Principle

To measure water content in insulating oil, we use Karl Fischer Titration. In this method, water (H2O) reacts chemically with iodine (I2), sulfur dioxide (SO2), an organic base (C5H5C), and alcohol (CH3OH) in an organic solvent.

The sample is mixed with sulfur dioxide, iodide ions, and an organic base/alcohol. Iodide ions are produced by electrolysis and participate in the reactions. As long as the reaction continues, no free iodide ions remain in the solution.

ef3b26676339f56a848ad8448b52b93c.jpeg

 The iodide ions produced by electrolysis are consumed as long as water molecules are present. When there is no more water to react, the Karl Fischer reactions stop. Two platinum electrodes in the solution detect this endpoint. The presence of iodide ions after the reaction changes the voltage-current ratio, indicating the reaction’s end.

According to Faraday law of electrolysis, the amount of iodine reacting is proportional to the electricity consumed for electrolysis during the Karl Fischer reactions. By measuring the electricity consumed until the reaction ends, we can calculate the actual mass of iodine involved. From the reaction equation, we know that one mole of iodine reacts with one mole of water. Therefore, 127 grams of iodine will react with 18 grams of water. This allows us to determine the exact amount of water in the insulating oil sample.

Electrolysis Role

Electrolysis produces iodide ions, which react with water in the solution.

Detection of Reaction Endpoint

Platinum electrodes detect the endpoint of the Karl Fischer reaction when no more water is present.

Calculation of Water Content

Using the electricity consumed during the reaction, the exact quantity of water in the insulating oil is calculated.

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.