• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Types & Characteristics of Surge Arresters

Edwiin
Field: Power switch
China

Introduction

Atmospheric lightning strikes on overhead lines, bare conductors, or metallic structures in outdoor substations, as well as overvoltages caused by switching operations of equipment and networks (switching overvoltages), pose significant hazards to electrical equipment. To protect equipment and facilitate insulation coordination, surge arresters (also known as "lightning arresters") must be installed at the incoming/outgoing points of overhead lines and in close proximity to transformers, due to their limited spatial protection zone.

Types and Characteristics of Surge Arresters

The most common surge arresters are non-linear metal oxide (MO) resistor type, housed in porcelain or silicone rubber. These are connected in parallel with the protected equipment and grounded via the earth grid. Another construction type uses silicon carbide (SiC) resistors (valve-type arresters), though these are less prevalent today.

Key Electrical Characteristics:

  • Resealing Voltage: The voltage across the arrester at which the follow current is reliably interrupted after sparkover.

  • Maximum Continuous Operating Voltage (MCOV): The highest power-frequency voltage (50 Hz or 60 Hz) that the arrester can withstand indefinitely.

  • Rated Short-Circuit Current: The maximum short-circuit current the arrester can safely handle.

  • Nominal Discharge Current: Common values include 5 kA, 10 kA, and 20 kA, indicating the arrester’s capacity to dissipate surge energy.

Surge arresters are connected between live conductors and ground. In installations with voltages above 52 kV, they may include discharge operation counters to monitor performance. An example of surge arresters is shown in Figure 1.

Additional Methods

In overhead lines and outdoor substations with voltages above 52 kV, it is common practice to install a lightning protection system comprising "lightning rods," "lightning aerial protection wires," or a combination of both.

LV Overvoltage Protection

Low Voltage (LV, where ) equipment, particularly electronic and informatics systems, is highly susceptible to severe damage from lightning discharges that propagate through cables or building structures.

To mitigate such risks, power surge protectors (SPDs) are typically installed in LV switchboards. These devices feature standard nominal discharge currents of 5 kA, 10 kA, and 20 kA, with some advanced models capable of handling 30–70 kA.

Similar to surge arresters, SPDs are connected between live conductors and ground, as illustrated in Figure 4. This configuration diverts surge currents away from sensitive equipment, ensuring protection against overvoltage events.

Give a tip and encourage the author!

Recommended

Analysis of Lightning Protection Measures for Distribution Transformers
Analysis of Lightning Protection Measures for Distribution TransformersTo prevent lightning surge intrusion and ensure the safe operation of distribution transformers, this paper presents applicable lightning protection measures that can effectively enhance their lightning withstand capability.1. Lightning Protection Measures for Distribution Transformers1.1 Install surge arresters on the high-voltage (HV) side of the distribution transformer.According to SDJ7–79 Technical Code for Overvol
12/24/2025
Transformer Protection Settings: Zero-Sequence & Overvoltage Guide
1. Zero-Sequence Overcurrent ProtectionThe operating current for zero-sequence overcurrent protection of grounding transformers is typically determined based on the transformer's rated current and the maximum allowable zero-sequence current during system ground faults. The general setting range is approximately 0.1 to 0.3 times the rated current, with operating time usually set between 0.5 to 1 second to quickly clear ground faults.2.Overvoltage ProtectionOvervoltage protection is a critical com
12/17/2025
Electrical Protection: Grounding Transformers and Bus Charging
1. High-Resistance Grounding SystemHigh-resistance grounding can limit ground fault current and appropriately reduce ground overvoltage. However, there is no need to connect a large high-value resistor directly between the generator neutral point and ground. Instead, a small resistor can be used together with a grounding transformer. The primary winding of the grounding transformer is connected between the neutral point and ground, while the secondary winding is connected to a small resistor. Ac
12/17/2025
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.