What is Medium Transmission Line?

Encyclopedia
Field: Encyclopedia
0
China


Medium Transmission Line Definition

A medium transmission line is defined as a transmission line with a length between 80 km (50 miles) and 250 km (150 miles).

A medium transmission line is defined as a transmission line with an effective length more than 80 km (50 miles) but less than 250 km (150 miles). Unlike a short transmission line, the line charging current of a medium transmission line is appreciable and hence the shunt capacitance must be considered (this is also the case for long transmission lines). This shunt capacitance is captured within the admittance (“Y”) of the ABCD circuit parameters.

The ABCD parameters of a medium transmission line are calculated using a lumped shunt admittance and a lumped series impedance. These parameters can be represented using three different models:

  • Nominal Π representation (nominal pi model)

  • Nominal T representation (nominal T model)

  • End Condenser Method

Let’s now go into the detailed discussion of these above-mentioned models, deriving the ABCD parameters for medium transmission lines.

Importance of Shunt Capacitance

Shunt capacitance is significant in medium transmission lines and must be considered due to the line charging current.

Nominal Π Mode

In case of a nominal Π representation (i.e. nominal pi model), the lumped series impedance is placed at the middle of the circuit whereas the shunt admittances are at the ends. As we can see from the diagram of the Π network below, the total lumped shunt admittance is divided into 2 equal halves, and each half with value Y ⁄ 2 is placed at both the sending and the receiving end while the entire circuit impedance is between the two.

2351050d37d828ed4cb297e7ebceb603.jpeg

 


The shape of the circuit so formed resembles that of a symbol Π, and for this reason, it is known as the nominal Π representation of a medium transmission line. It is mainly used for determining the general circuit parameters and performing load flow analysis.

Here, VS is the supply end voltage, and VR is the receiving end voltage. Is is the current at the supply end, and IR is the current at the receiving end. I1 and I3 are the currents through the shunt admittances, and I2 is the current through the series impedance Z.

Now applying KCL, at node P, we get.

Similarly applying KCL, to node Q.

Now substituting equation (2) to equation (1)

Now by applying KVL to the circuit,

799617e62b15c3c9b3e26999b13ec0d4.jpeg

 

Comparing equation (4) and (5) with the standard ABCD parameter equations

We derive the ABCD parameters of a medium transmission line as:


12c19d4b65a0ca8b6842e0234e4bb82a.jpeg

 


Nominal T Model

In the nominal T model of a medium transmission line the lumped shunt admittance is placed in the middle, while the net series impedance is divided into two equal halves and placed on either side of the shunt admittance. The circuit so formed resembles the symbol of a capital T, and hence is known as the nominal T network of a medium length transmission line and is shown in the diagram below.


e86bf1f74c9e7f4570fd70f77f9e7455.jpeg

Here also Vt networks and Vr is the supply and receiving end voltages respectively, and

Is is the current flowing through the supply end.

Ir is the current flowing through the receiving end of the circuit.

Let M be a node at the midpoint of the circuit, and the drop at M, be given by Vm.

Applying KVL to the above network we get,

Now the sending end current is,

Substituting the value of VM to equation (9) we get,

1a7469bf5bbd7d3615d9014ea659f8c8.jpeg

Again comparing equation (8) and (10) with the standard ABCD parameter equations,

The parameters of the T network of a medium transmission line are

5943304bad9132e0d4710ce8bc6ded47.jpeg

 


ABCD Parameters

The ABCD parameters for medium transmission lines are calculated using the lumped shunt admittance and series impedance, crucial for analyzing and designing these lines.

End Condenser Method

In the end condenser method, the line capacitance is concentrated at the receiving end. This method tends to overestimate the effects of capacitance

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.