Sag and Tension

Edwiin
Field: Power switch
China

For safety purpose, the ground clearance of the conductors at maximum temperature and minimum loading condition should be maintained. Analysis of the sag and tension is important in the transmission line for the continuity and quality of electrical services. If the tension of the conductor is increased beyond the limit, it may get broken, and the power transmission of the system get erupt.

The dip of the conductor between the two level supports is called sag. In other words, the vertical distance between the highest point of the electrical pole or tower (where the conductor is connected) and the lowest point of the conductor between the two adjacent level supports is known as sag shown in the figure below. The horizontal distance between two electrical supports is called the span.

If the weight of a conductor is evenly distributed along the line, a freely - suspended conductor is assumed to take the shape of a parabola. The magnitude of the sag increases as the span length grows. For small spans (up to 300 meters), the parabolic method is employed for calculating sag and tension, while for large spans (such as river crossings), the catenary method is used.
Factors Affecting the Sag

  • Conductor Weight: The sag of a conductor is directly proportional to its weight. Ice loading can increase the weight of the conductors, thereby increasing the sag.

  • Span: Sag is directly proportional to the square of the span length. Longer spans result in greater sag.

  • Tension: Sag is inversely proportional to the tension in the conductor. Higher tension, however, increases the stress on insulators and supporting structures.

  • Wind: Wind causes an increase in sag in an inclined direction.

  • Temperature: Sag decreases at low temperatures and increases at higher temperatures.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025