Energy Meter with Lag Adjustment Devices

Encyclopedia
Field: Encyclopedia
0
China

Energy Meter Definition


An energy meter is a device that measures electric energy consumption.


Lag Adjustment in Energy Meter


In induction type energy meters, the rotation speed should match the power by keeping the phase angle between the supply voltage and pressure coil flux at 90 degrees. In reality, this angle is slightly less than 90 degrees. Lag adjustment devices help correct this phase angle. Let’s consider the figure beside:


c46930f3254bee1a958d1ece6217d3ee.jpeg


In the figure, another coil called the lag coil is introduced on the central limb with turns equal to N. When the supply voltage is given to the pressure coil, it produces flux F, which splits into Fp and Fg. The Fp flux cuts the moving disc and links with the lag coil, inducing an emf El that lags Fp by 90 degrees. 


The current Il also lags Fl by 90 degrees, and the lag coil produces flux Fl . The resultant flux cutting the disc combines Fl and Fp , aligning with the resultant mmf of the lag or shading coil. The mmf of the shading coil can be adjusted by two methods:


  • By adjusting electrical resistance.

  • By adjusting shading bands.


Let us discuss these points in more detail:

Adjustment of coil resistance:


2c436ba4736b5bc5187cabee59e5327a.jpeg


If the coil’s electrical resistance is high, the current will be low, decreasing the coil’s mmf and the lag angle. Lowering the resistance by using thicker wire in coils can adjust the lag angle. Adjusting electrical resistance indirectly changes the lag angle.


By adjusting the shading bands up and down on the central limb we can adjust lag angle because when we move shading bands upward, then they embrace more flux hence the induced emf increases therefore mmf increases with increase in the value of lag angle. 


When we move shading bands downwards then it will embrace less flux hence the induced emf will decrease therefore mmf decreases with decrease in the value of lag angle. So by adjusting the position of shading bands we can adjust the lag angle.


Friction Compensation


1765985f53ea53060bcd3d6ef299efb2.jpeg


To compensate for friction, a small force is applied in the disc’s rotation direction, which should be load-independent for accurate readings at light loads. Overcompensation can cause creeping, defined as the disc’s continuous rotation by energizing the pressure coil with no current in the current coil. 


To prevent creeping, two holes are drilled opposite each other on the disc, distorting the eddy current path. This shifts the center of the eddy current paths from C to C1, creating a magnetic pole at C1. The disc will creep until the hole reaches the pole’s edge, where the rotation is stopped by the opposing torque.


Overload Compensation


Under load conditions, the disc continuously moves, inducing a dynamically induced emf due to rotation. This emf generates eddy currents that interact with the series magnetic field to produce a breaking torque. This breaking torque, proportional to the square of the current, increases and opposes the disc’s rotation.


 To avoid this self-breaking torque, the disc’s full load speed is kept low. Errors in single-phase energy meters are caused by both the driving and braking systems and can be separated as follows:


Error caused by Driving System


  • Error Due to Non SymmetricalMagnetic Circuit:If the magnetic circuit is not symmetrical there produce a driving torque, due to which meter creep.



  • Error Due to Wrong Phase Angle:If there is not a proper phase difference between the various phasors then it results in improper rotation of disc. Improper phase angle is due to improper lagadjustment, variation of resistance with temperature or it may be due to abnormal frequency of supply voltage.


  • Error Due to Wrong Magnitude of Fluxes:There are several reasons for wrong magnitude of fluxes out of these main reasons are abnormal values of current and voltage.

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.