• SF6-free gas-insulated switchgear for primary distribution
SF6-free gas-insulated switchgear for primary distribution
discuss personally
Model
ZX2-24
ZX2-17.5
ZX2-12
Basic info
Brand ABB
Model NO. SF6-free gas-insulated switchgear for primary distribution
Rated voltage 24kV
Rated frequency 50/60Hz
Series PrimeGear ZX2
Product Detail

Customer benefits:

Compliant with IEC standards and F-gas regulation

  •  Compliant with IEC standards and with the EU F-gas regulation (EU) 2024/573.

  •  High ratings up to 2500A. Single busbar modular and compact lowpressure design, based on natural origin gases (SF6 free).

  •  Loss of service continuity LSC 2A  and partition class PM*.

Reliable and flexible 

  • Compact and modular design for space optimization. 

  • Very low maintenance required as all high voltage parts are permanently sealed in a gas tank and protected from soiling, humidity, foreign bodies, and other environmental influences.

  • Due to the low-pressure design,  the switchgear can remain in service  up to the point of repair, even in the unlikely event of a leak. 

  • The switchgear can be enabled with monitoring and diagnostics (e.g., temperature, gas, partial discharge)  to track asset health. Automation and control features based on current and voltage sensors and IEC 61850 protocol allow for customization during the manufacturing phase and varying loads during operations.

  • Well known and proven vacuum circuit breaker type VD4X. 

  • Outer cone cable termination system.

Safety 

  •  High level of operator safety with front, lateral and rear arc protection,  certified AFL(R) 40kA 1s (according to IEC 62271-200). 

  • Plug-in busbar technology and the factory-assembled pressure relief duct allows for safe, quick and easy installation at site. 

  • With the switchgear diagram and operation controls on the front panel, no opening of the doors  is required for manual operation making the switchgear operator friendly.

  •  Wide range of monitoring and diagnostic features for safe and reliable operations. All switching devices are motor-operated and  can be controlled remotely.

  •  Mechanical and electrical interlocks prevent incorrect operation of the switchgear panels.

Technical parameters:

Structure diagram:

 

 

Know your supplier
ABB
As an authorized distributor of ABB products, we take great pride in our partnership.
Main Categories
High Voltage Electrical Apparatus/Low Voltage Electrical Apparatus
Business Type
Sales
Highest Annual Export (USD)
$580000000
Professional Experience
11 years
Workplace
20000m²
占位
占位
Documents
Public.
SF6-free gas-insulated switchgear for primary distribution
Manual English
PDF
FAQ
Q: What’s the difference in the circuit breaker for air-insulated vs gas-insulated?
A:
Air-insulated switchgear circuit breaker is typically removable or withdrawable. The circuit breaker is based on vacuum circuit technology. In the gas-insulated, it is fixed mounted. The function of withdraw is provided by a separate disconnecting switch. Typically, a three-position switch with connected, disconnected, and ready-to-earth position.
Q: What’s the difference in the circuit breaker for air-insulated vs gas-insulated?
A:
Air-insulated switchgear circuit breaker is typically removable or withdrawable. The circuit breaker is based on vacuum circuit technology. In the gas-insulated, it is fixed mounted. The function of withdraw is provided by a separate disconnecting switch. Typically, a three-position switch with connected, disconnected, and ready-to-earth position.
Q: What are the maintenance requirements associated with the air-insulated switchgear (AIS) vs gas-insulated (GIS)?
A:
Gas-insulated switchgear requires very low maintenance as all high voltage parts are permanently protected in a gas tank from soiling, humidity, entry of foreign bodies and other environmental influences. Primary, the drives located outside gas compartment require inspection and maintenance. On the other hand, gas-insulated switchgear repair requires additional training (e.g. for gas works) and the replacement or parts may not be as easily. In the air-insulated switchgear visual inspection is recommended in regular intervals, maintenance of power parts is given in installation, operation and maintenance manual (1VLM000363).
Q: What smart solutions are available for ABB’s AIS portfolio?
A:
ABB’s switchgear smart solutions are designed to help our customers make data-driven decisions. Our customers can benefit from a wide range monitoring, diagnostic, automation and control features for their ABB’s air-insulated medium voltage switchgear. Contact our sales team to learn more about ABB’s smart solutions for each of our switchgear.
Related Products
Related Knowledges
How is the contradiction between the small grounding residual current and the neutral point displacement voltage exceeding the standard resolved?
How is the contradiction between the small grounding residual current and the neutral point displacement voltage exceeding the standard resolved?
Contradiction PointsIn automatic tracking arc suppression coils, the adjustment precision is high, the residual current is small, and the operation is close to the resonance point.In an automatic tracking arc suppression coil grounding system, two factors must be considered: Under normal operating conditions, the long-term voltage displacement of the neutral point should not exceed 15% of the system's nominal phase voltage; In the case of a ground fault, the grounding residual current should be
Edwiin
07/28/2025
Power Supply Design of the Group Testing Device for Special Transformers in Electrified Railways
Power Supply Design of the Group Testing Device for Special Transformers in Electrified Railways
1 Hardware Design of Tester Power SupplyThis device uses a standard small - signal generating device to generate small - current signals with the required frequency and phase angle. Then, through the amplifying circuit and phase - modulating circuit, the working power supply is generated.1.1 Power Frequency Sine Wave Small - Current Signal Generating DeviceThe sine wave generating circuit is mainly composed of the waveform generating chip MAX038 produced by MAXIM Corporation of the United States
Ron
07/28/2025
Analysis of Testing Methods for Turns Ratio and Connection Mode of Special Transformers
Analysis of Testing Methods for Turns Ratio and Connection Mode of Special Transformers
1 Error Analysis of Traditional Turn Ratio Testing MethodsThe QJ35 turn ratio bridge and other single-phase-phase-based testers all use the double-voltmeter principle. The QJ35, however, eliminates power supply fluctuation interference via bridge balance. For three-phase transformer ratio testing with a single power supply, corresponding terminals must be shorted and data converted, turning three-phase tests into independent single-phase measurements, with √3 Yd conversion based on connect
Felix Spark
07/28/2025
What are the production processes of special transformers?
What are the production processes of special transformers?
A certain special transformer manufacturing enterprise, which has been producing special transformers such as split - phase - shifting rectifier transformers, rectifier transformers for electrolysis, and transformers for submerged arc furnaces for more than 20 years. Now, an evaluation is made on the production process flow and its characteristics of the special transformers after the company's transformation.1.Production Process Flow Chart of Special TransformersThe production of special transf
Leon
07/28/2025
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con