| Brand | Wone Store |
| Model NO. | CYEVT1-24 Electronic Current Transformer |
| Rated frequency | 50/60Hz |
| Rated insulation voltage | 24kV |
| Series | CYEVT |
Product Overview
The products accord with standard IEC60044-8, GB/T20840.8-2007, and can meet customer’s other special requirement. The products use Rogowski winding to test current, mainly used in ≤ 20kV switchgear, match with electric instrument, digital measure and protective equipment, can at the same time realize multi-functions such as measure, control, protection and data transmission etc, secondary open circuit can not produce high voltage.
Main techinical parameter
Rated primary voltage:22kV
Rated primary current : 50-2000A
Rated secondary voltage : 4V(measure),200mV(protective)
Rated digital output : 0x2D41(measure) 0x01CF(protective)
Accuracy for measure winding : 0.2
Accuracy for protective winding : 5P20
Rated frequency : 50Hz
Rated insulation level : 24/65/125kV
Rated short time thermal current : 50-200A: 150Ipr, 300-2000A :31.5kA/1S
Rated dynamic current : 50-200A :375Ipr, 300-2000A :80kA
Ambient temperature : -5℃ -40℃ (indoor), -25℃-50℃(outdoor)
Ambient humidity : ≤RH95%(25℃ )
Altitude : ≤ 2000m (Can devise according customer’s requirement)
Installation site : indoor/ outdoor
Outline drawing